Calculators
Three calculators that answer the questions we get asked most on a quote call. Run it, then send us the result.
Pick one
Each page shows the formula, what to do with the result, and where the shortcuts break down.
You have a load current and a voltage. You need a transformer rating. Returns kVA plus the next standard size with headroom.
The one-line shows kW. Transformers are rated in kVA. Pick the power factor for the load type and get the rating.
Available secondary fault current from kVA, secondary voltage, and nameplate impedance. The number the breaker AIC rating has to beat.
Before you trust the number
The math is right. The inputs are yours. Three things change the answer more than the formula does.
A 480 V service sized to today's amps is full the day the next building opens. We size padmounts with headroom by default and say so on the quote.
Fault current moves with %Z. A 5.75% unit and a 3.5% unit at the same kVA give very different breaker ratings. Use the nameplate, not the typical.
Drives, rectifiers, and GPU halls need K-factor or derated units. The kVA is the start of the spec, not the end of it.