Amps to kVA

Amps to kVA calculator.

Turn a load current and a system voltage into a transformer rating. Single or three phase. The result includes the next standard kVA size and the size with headroom.

Amps to kVA

V
A

0kVA
–Next standard size
–Standard size with headroom

Standard sizes follow the common three-phase (15 to 10000 kVA) and single-phase (10 to 833 kVA) ratings. Confirm against the spec.

Formula

Two formulas. One √3.

Apparent power is volts times amps. Three-phase systems carry √3 (1.732) because the line voltage is measured across two phases.

Three phasekVA = (A × V × 1.732) ÷ 1000
Single phasekVA = (A × V) ÷ 1000
Back to amps (3φ)A = (kVA × 1000) ÷ (V × 1.732)
  • ALoad current in amps. Use the full-load or design current, not the breaker frame.
  • VLine-to-line voltage for three phase. Line-to-neutral for a single-phase, two-wire load.
  • 1.732Square root of three. Only applies to three-phase.
  • kVAApparent power. Transformers are rated in kVA because the transformer does not know the power factor of what is hung on it.

After the number

What the kVA does not settle.

The rating is the first line of the transformer spec. Four more lines decide the price and the lead time.

  • 01Primary and secondary voltage

    480Y/277 V secondary is stock. 12470V or 34500V primary is a question. Both change the quote.

  • 02Headroom

    A padmount that runs at 100% from day one is a padmount that gets replaced. 25% is our default; 35% for a phased campus.

  • 03Load type

    Drives, rectifiers, and GPU racks pull harmonics. That is a K-factor or a derate, and it is cheaper to spec it now than to swap it later.

  • 04Stock or built

    Standard sizes at 480Y/277 ship from stock in days. Odd voltages and taps are built to order in 6 to 9 weeks.

Reference

Full-load amps at common voltages.

Three-phase, at unity. Use it to sanity-check the calculator or read backwards from a breaker size.

kVA208 V480 V4160 V12470 V
752089010.43.5
15041618020.86.9
30083336141.613.9
500138860169.423.1
750208290210434.7
10002776120313946.3
15004164180420869.4
20005551240627892.6
250069393007347116
3750104094511520174

Amps = kVA × 1000 ÷ (V × 1.732). Rounded to the nearest amp.

FAQ

The questions that follow the number.

Which voltage do I enter, primary or secondary?

The side the load is on. If you know the 480 V load current, enter 480 and the secondary amps. The kVA is the same on both sides of the transformer; only the current changes.

Is this kVA or kW?

kVA. Real power (kW) is kVA times the power factor. A transformer has to carry the full kVA, so that is the rating that matters for sizing. Use the kW to kVA calculator if the one-line only gives kW.

What about single-phase 240/120?

Select 1-phase and enter 240 V with the current on the 240 V side. Three-wire single-phase padmounts are rated the same way.

Does the calculator account for demand or diversity?

No. It converts the current you enter. If the connected load is 1200 A but the demand study says 800 A, enter the number the engineer of record is designing to.

How accurate is the standard-size lookup?

It picks the first common rating at or above the result. Some manufacturers skip sizes or add 2000 and 3000 kVA in one line and not another. The quote confirms what is available from stock.