Amps to kVA
Turn a load current and a system voltage into a transformer rating. Single or three phase. The result includes the next standard kVA size and the size with headroom.
Standard sizes follow the common three-phase (15 to 10000 kVA) and single-phase (10 to 833 kVA) ratings. Confirm against the spec.
Formula
Apparent power is volts times amps. Three-phase systems carry √3 (1.732) because the line voltage is measured across two phases.
kVA = (A × V × 1.732) ÷ 1000kVA = (A × V) ÷ 1000A = (kVA × 1000) ÷ (V × 1.732)After the number
The rating is the first line of the transformer spec. Four more lines decide the price and the lead time.
480Y/277 V secondary is stock. 12470V or 34500V primary is a question. Both change the quote.
A padmount that runs at 100% from day one is a padmount that gets replaced. 25% is our default; 35% for a phased campus.
Drives, rectifiers, and GPU racks pull harmonics. That is a K-factor or a derate, and it is cheaper to spec it now than to swap it later.
Standard sizes at 480Y/277 ship from stock in days. Odd voltages and taps are built to order in 6 to 9 weeks.
Reference
Three-phase, at unity. Use it to sanity-check the calculator or read backwards from a breaker size.
| kVA | 208 V | 480 V | 4160 V | 12470 V |
|---|---|---|---|---|
| 75 | 208 | 90 | 10.4 | 3.5 |
| 150 | 416 | 180 | 20.8 | 6.9 |
| 300 | 833 | 361 | 41.6 | 13.9 |
| 500 | 1388 | 601 | 69.4 | 23.1 |
| 750 | 2082 | 902 | 104 | 34.7 |
| 1000 | 2776 | 1203 | 139 | 46.3 |
| 1500 | 4164 | 1804 | 208 | 69.4 |
| 2000 | 5551 | 2406 | 278 | 92.6 |
| 2500 | 6939 | 3007 | 347 | 116 |
| 3750 | 10409 | 4511 | 520 | 174 |
Amps = kVA × 1000 ÷ (V × 1.732). Rounded to the nearest amp.
FAQ
The side the load is on. If you know the 480 V load current, enter 480 and the secondary amps. The kVA is the same on both sides of the transformer; only the current changes.
kVA. Real power (kW) is kVA times the power factor. A transformer has to carry the full kVA, so that is the rating that matters for sizing. Use the kW to kVA calculator if the one-line only gives kW.
Select 1-phase and enter 240 V with the current on the 240 V side. Three-wire single-phase padmounts are rated the same way.
No. It converts the current you enter. If the connected load is 1200 A but the demand study says 800 A, enter the number the engineer of record is designing to.
It picks the first common rating at or above the result. Some manufacturers skip sizes or add 2000 and 3000 kVA in one line and not another. The quote confirms what is available from stock.