Fault current
Available secondary fault current at the transformer terminals from kVA, secondary voltage, and nameplate impedance. This is the number the main breaker's interrupting rating has to beat.
Infinite-bus calculation: assumes unlimited utility fault current and zero conductor impedance. That is the conservative number for breaker interrupting ratings at the transformer terminals.
Formula
A bolted fault on the secondary is limited only by the transformer's own impedance when the utility source is treated as infinite. Lower %Z means more fault current.
FLA = (kVA × 1000) ÷ (V × 1.732)FLA = (kVA × 1000) ÷ VIsc = FLA ÷ (%Z ÷ 100)Reference
Use the nameplate when you have it. When you are pricing before the unit exists, these are the ranges the industry designs to.
| Transformer | Typical %Z | Why it matters |
|---|---|---|
| Padmount 75 – 300 kVA | 1.5 – 3.5% | Low %Z means very high fault current at 208/480 V; 65 kA mains are common |
| Padmount 500 – 1000 kVA | 3.0 – 5.75% | Most 480 V services land here; 42 to 65 kA breaker ratings |
| Padmount 1500 – 2500 kVA | 5.75% | ANSI standard; 2500 kVA at 480 V gives about 52 kA |
| Padmount 3000 – 5000 kVA | 5.75 – 7.0% | Higher %Z is specified on purpose to keep secondary fault current under 65 kA |
| MV substation 5 – 30 MVA | 6.5 – 10% | Fault current is limited by design; coordination studies take over |
Impedance tolerance is ±7.5% of the nameplate value per IEEE C57.12.00. Use the low end for a conservative breaker rating.
After the number
Available fault current shows up in the breaker spec, on the label, and in the coordination study.
The main and every downstream breaker must be rated at or above the available fault current at its terminals. 480 V mains at 2500 kVA and 5.75% need a 65 kA frame, not 42.
Service equipment has to be marked with the available fault current and the date of the calculation. This calculator gives the transformer-terminal number; conductors between the transformer and the gear bring it down.
Once the available fault current is known, the engineer decides between fully rated and series-rated gear. Higher %Z at the transformer often saves more on downstream gear than it costs on copper.
FAQ
Short answers. If yours is not here, the quote desk picks up.
Full-load current is what the transformer delivers at nameplate. Available fault current is what it can deliver for a few cycles into a dead short, typically 15 to 40 times more. Breakers are rated for the second number.
The infinite-bus method assumes the utility can supply unlimited current on the primary. It is the worst case and the one most AHJs accept for the transformer terminals. A utility contribution of, say, 150 MVA at 12.47 kV will lower the result a few percent.
Yes, a lot. 100 feet of 500 kcmil between a 2500 kVA padmount and the switchboard can cut the fault current by 20 to 30%. This calculator gives the number at the transformer. A point-to-point calculation gives the number at the gear.
Specify a higher impedance transformer, split the load across two smaller units, add conductor length, or use current-limiting fuses or breakers. The first option is the cheapest and it is a line on the RFQ.
Every time. A 1500 kVA at 5.75% replaced with a 2000 kVA at 5.75% raises the available fault current by a third. The label and the breaker ratings both change.