Fault current

Fault current calculator.

Available secondary fault current at the transformer terminals from kVA, secondary voltage, and nameplate impedance. This is the number the main breaker's interrupting rating has to beat.

Fault current

kVA
%Z
V

0A available
–Full-load amps (secondary)
–Minimum breaker AIC (next standard)

Infinite-bus calculation: assumes unlimited utility fault current and zero conductor impedance. That is the conservative number for breaker interrupting ratings at the transformer terminals.

Formula

Full-load amps, divided by impedance.

A bolted fault on the secondary is limited only by the transformer's own impedance when the utility source is treated as infinite. Lower %Z means more fault current.

Full-load amps (3φ)FLA = (kVA × 1000) ÷ (V × 1.732)
Full-load amps (1φ)FLA = (kVA × 1000) ÷ V
Available fault currentIsc = FLA ÷ (%Z ÷ 100)
  • kVATransformer nameplate rating. Use the base (ONAN) rating, not the fan-cooled rating.
  • VSecondary line-to-line voltage.
  • %ZNameplate impedance. Padmounts typically run 1.5 to 6%. Larger units and substation transformers 5.75 to 8%.
  • IscSymmetrical RMS fault current at the secondary terminals, infinite primary source.

Reference

Typical impedance by size.

Use the nameplate when you have it. When you are pricing before the unit exists, these are the ranges the industry designs to.

TransformerTypical %ZWhy it matters
Padmount 75 – 300 kVA1.5 – 3.5%Low %Z means very high fault current at 208/480 V; 65 kA mains are common
Padmount 500 – 1000 kVA3.0 – 5.75%Most 480 V services land here; 42 to 65 kA breaker ratings
Padmount 1500 – 2500 kVA5.75%ANSI standard; 2500 kVA at 480 V gives about 52 kA
Padmount 3000 – 5000 kVA5.75 – 7.0%Higher %Z is specified on purpose to keep secondary fault current under 65 kA
MV substation 5 – 30 MVA6.5 – 10%Fault current is limited by design; coordination studies take over

Impedance tolerance is ±7.5% of the nameplate value per IEEE C57.12.00. Use the low end for a conservative breaker rating.

After the number

Three things the number feeds.

Available fault current shows up in the breaker spec, on the label, and in the coordination study.

  • 01Breaker interrupting rating

    The main and every downstream breaker must be rated at or above the available fault current at its terminals. 480 V mains at 2500 kVA and 5.75% need a 65 kA frame, not 42.

  • 02NEC 110.24 label

    Service equipment has to be marked with the available fault current and the date of the calculation. This calculator gives the transformer-terminal number; conductors between the transformer and the gear bring it down.

  • 03Series ratings and coordination

    Once the available fault current is known, the engineer decides between fully rated and series-rated gear. Higher %Z at the transformer often saves more on downstream gear than it costs on copper.

FAQ

The questions that follow the number.

Short answers. If yours is not here, the quote desk picks up.

What is the difference between available fault current and full-load current?

Full-load current is what the transformer delivers at nameplate. Available fault current is what it can deliver for a few cycles into a dead short, typically 15 to 40 times more. Breakers are rated for the second number.

Why does the calculator ignore the utility?

The infinite-bus method assumes the utility can supply unlimited current on the primary. It is the worst case and the one most AHJs accept for the transformer terminals. A utility contribution of, say, 150 MVA at 12.47 kV will lower the result a few percent.

Does conductor length matter?

Yes, a lot. 100 feet of 500 kcmil between a 2500 kVA padmount and the switchboard can cut the fault current by 20 to 30%. This calculator gives the number at the transformer. A point-to-point calculation gives the number at the gear.

How do I reduce the fault current?

Specify a higher impedance transformer, split the load across two smaller units, add conductor length, or use current-limiting fuses or breakers. The first option is the cheapest and it is a line on the RFQ.

Do I recalculate if the transformer is swapped?

Every time. A 1500 kVA at 5.75% replaced with a 2000 kVA at 5.75% raises the available fault current by a third. The label and the breaker ratings both change.

Need a specific %Z? Put it on the spec. We price to it.